Voltage Drop Formula

There is really only one voltage drop formula. What changes between DC, single-phase and three-phase is a single multiplier, and what changes between the various forms you see written down is whether resistance is looked up in a table or worked out from the conductor area.

The one formula

Every voltage drop calculation on this site, and in every textbook, reduces to Ohm’s law applied along a conductor:

V_drop = k × I × Z × L
V_drop
Voltage lost in the conductors · volts
k
2 for DC and single-phase, √3 for balanced three-phase
I
Load current · amperes
Z
Conductor impedance per unit length · Ω per 1000 ft
L
One-way run length · thousands of feet

Everything below is this equation with something substituted in. Pick the right k for your system, get Z right for your conductor and load, and measure L one way rather than there and back, and the answer follows.

DC circuits

Direct current
V_drop = 2 × I × R × L
R
Conductor resistance · Ω per 1000 ft

DC is the simplest case. There is no reactance, no power factor and no phase angle: the only thing opposing current is resistance, so Z is just R. This makes the DC formula exact rather than approximate. Whatever error there is in the answer comes from not knowing the current, the length or the conductor temperature precisely, never from the formula itself.

Because low-voltage DC systems draw high current for modest power and are compared against a small supply voltage, the percentage drop climbs fast. A 12 V circuit losing half a volt has already lost 4.2%. See the DC voltage drop calculator for the sizes and distances that go with common battery and solar voltages.

Single-phase AC

Single-phase alternating current
V_drop = 2 × I × Z_e × L
Z_e
Effective impedance · Ω per 1000 ft

The multiplier is the same 2 as DC, for the same reason: a two-wire circuit carries the full load current out along one conductor and back along the other. What changes is that Z is now an impedance rather than a plain resistance, because an alternating current sets up a magnetic field around the conductor and that field opposes changes in the current.

At unity power factor (a heater, an incandescent lamp), the reactive part contributes nothing and Z_e collapses back to R. The further the load is from unity, the more the reactance matters.

Three-phase AC

Balanced three-phase alternating current
V_drop = √3 × I × Z_e × L
√3
Approximately 1.7320508
I
Line current in one phase conductor · amperes

This gives the line-to-line voltage drop, which is what you compare against a line-to-line supply voltage like 208 V, 400 V or 480 V. If you need the line-to-neutral drop on a balanced system, divide the result by √3, or calculate with the line-to-neutral voltage and a multiplier of 1. Mixing the two is a common way to produce an answer that is out by 73%.

Where 2 and √3 come from

This is the part most explanations skip, and it is the part worth understanding because it stops you ever picking the wrong one.

The 2

In a two-wire circuit, whether DC or single-phase, the current has to complete a loop. It leaves the source, travels the length of the run through one conductor, passes through the load, and returns the length of the run through the other. So the current passes through two run-lengths of conductor, and each contributes I × R × L of drop. Total: 2 × I × R × L.

The √3

In a balanced three-phase circuit there is no dedicated return conductor. Each of the three line currents is 120° out of phase with the others, and at every instant they sum to zero: each conductor acts as the return path for the other two. Current therefore traverses only one run-length per phase.

That gives a line-to-neutral drop of I × Z × L. But three-phase supplies are quoted line-to-line, and a line-to-line voltage is √3 times the line-to-neutral voltage. Scaling the drop the same way gives √3 × I × Z × L.

Impedance and power factor

For AC, the conductor opposes current with resistance R and inductive reactance X_L. The two act at right angles to each other, but voltage drop is not the magnitude of that combination. It is the component of the conductor impedance lying in the direction of the load current:

Effective impedance
Z_e = R × cos θ + X_L × sin θ
R
AC resistance of the conductor · Ω per 1000 ft
X_L
Inductive reactance at 60 Hz · Ω per 1000 ft
θ
Power factor angle, arccos(PF) · degrees or radians
cos θ
The power factor itself, 0 to 1
sin θ
√(1 − PF²)

This is stated in the notes to NEC Chapter 9, Table 9, which also publishes an effective-impedance column computed at 0.85 power factor. Recomputing that column from the table’s own R and X_L values is one of the checks the calculation engine on this site is tested against.

Note what happens at the extremes. At PF = 1, cos θ = 1 and sin θ = 0, so Z_e = R: reactance drops out entirely. At PF = 0.7, sin θ is about 0.71, so the reactance term is contributing nearly as much as it possibly can. This is why a resistance-only estimate is exactly right for a resistive load and progressively optimistic for a motor.

The AC calculator shows how much a resistance-only figure understates the drop across the whole power factor range.

The circular-mil K method

The form most often taught in the trade avoids looking anything up. Instead of a tabulated resistance it uses the conductor’s cross-sectional area in circular mils and a constant that carries the resistivity of the metal:

Single-phase, circular mils
V_drop = (2 × K × I × L) ÷ cmil
Three-phase, circular mils
V_drop = (√3 × K × I × L) ÷ cmil
K
Resistance of a conductor 1000 cmil in area and 1000 ft long, at 75 °C · 12.9 copper, 21.2 aluminium
I
Load current · amperes
L
One-way run length · feet
cmil
Conductor area · circular mils

Note that L here is in plain feet, not thousands of feet: the K constant absorbs the factor of 1000. That difference between the two forms is worth watching for.

How the two methods compare

Take 20 A on 12 AWG copper over 100 ft, single-phase. 12 AWG is 6530 circular mils.

Table method against K method for the same circuit
MethodWorkingResult
Table2 × 20 × 1.98 × 0.17.92 V
K constant(2 × 12.9 × 20 × 100) ÷ 65307.90 V

A 0.3% difference, which is the rounding in the K constant. Both are fine for design work. The table method wins when you want the actual published resistance for a specific stranding and temperature; the K method wins when you are working from a conductor area and have no table to hand.

The metric form

Outside North America, resistance is quoted in ohms per kilometre and conductor areas in mm². The formula takes the same shape with resistivity in place of a constant:

Metric, from resistivity
V_drop = (k × ρ × L × I) ÷ A
ρ
Resistivity at operating temperature · Ω·mm²/m (0.0209 copper, 0.0345 aluminium at 75 °C)
L
One-way run length · metres
A
Conductor cross-sectional area · mm²
k
2 for DC and single-phase, √3 for three-phase

Worked through: 20 A on 4 mm² copper over 30 m, single-phase, gives (2 × 0.0209 × 30 × 20) ÷ 4 = 6.27 V. On a 230 V supply that is 2.7%.

Where resistance comes from

Resistance is not a property of a wire alone: it depends on the metal, the cross-sectional area, the length and the temperature:

Resistance of a conductor
R = ρ × L ÷ A
ρ
Resistivity of the metal at temperature · Ω·m
L
Conductor length · m
A
Cross-sectional area · m²

At 20 °C, copper is 1.7241 × 10⁻⁸ Ω·m. This value is the definition of 100% IACS, the conductivity standard everything else is measured against. Aluminium used in conductors is 61% IACS, which works out to 2.8264 × 10⁻⁸ Ω·m.

Resistivity rises with temperature, and the correction that goes with the standard reference tables is:

Temperature correction, referenced to 75 °C
R₂ = R₁ × [1 + α × (T₂ − 75)]
R₁
Resistance at 75 °C, from the table · Ω
T₂
Operating temperature · °C
α
Temperature coefficient at 75 °C · 0.00323 copper, 0.00330 aluminium

Going from 75 °C to 90 °C raises copper resistance, and therefore voltage drop, by about 4.8%. Running cool works the other way: at 25 °C, resistance is about 16% lower than the tabulated figure.

Percentage and load voltage

Percentage drop
%V_drop = (V_drop ÷ V_source) × 100
Voltage reaching the load
V_load = V_source − V_drop

The percentage is what design limits are written against, and it is why the same volts lost matter far more at 12 V than at 480 V. Half a volt is 4.2% of a 12 V supply and 0.1% of a 480 V one.

Rearranged for size and length

The formula has one unknown appearing once and linearly, so it rearranges exactly for whichever quantity you actually need.

Maximum impedance for a given drop limit
Z_max = (V_source × limit ÷ 100) ÷ (k × I × L)

Take the smallest listed conductor whose impedance is at or below this figure. That is what the wire size calculator does.

Maximum run length for a given drop limit
L_max = (V_source × limit ÷ 100) ÷ (k × I × Z)

The answer is in the same length unit as Z is quoted per: thousands of feet, if Z is in Ω per 1000 ft. This is what the maximum cable length calculator computes.

Minimum conductor area, circular mils
cmil_min = (k × K × I × L) ÷ V_allowed

Every variable

Symbols used in the voltage drop formulas on this page
SymbolMeaningUnit
V_dropVoltage lost in the conductorsV
V_sourceSupply voltage, line-to-line for three-phaseV
V_loadVoltage remaining at the loadV
ILoad current, per phase conductorA
RConductor resistance per unit lengthΩ/1000 ft or Ω/km
X_LInductive reactance per unit length at 60 HzΩ/1000 ft
Z_eEffective impedance, R cos θ + X sin θΩ/1000 ft
LOne-way run length, source to load1000 ft, ft or m
kSystem multiplier2 or √3
KCircular-mil resistivity constant at 75 °C12.9 Cu, 21.2 Al
cmilConductor cross-sectional areacircular mils
AConductor cross-sectional areamm²
ρResistivity of the conductor metalΩ·m or Ω·mm²/m
αTemperature coefficient of resistanceper °C
θPower factor angle, arccos(PF)degrees
PFPower factor, cos θ0 to 1
nConductors in parallel per phasecount

Questions

What is the voltage drop equation?

V_drop = k × I × Z × L. The current I in amperes multiplied by the conductor impedance Z per unit length, multiplied by the one-way run length L, multiplied by a factor k that is 2 for DC and single-phase circuits and √3 for balanced three-phase. It is Ohm’s law with the geometry of the circuit folded into k.

Why is the three-phase formula 1.732 instead of 2?

Because a balanced three-phase circuit has no conductor carrying the full return current. In a two-wire circuit the current goes out along one conductor and back along the other, so it traverses twice the run length, hence 2. In a balanced three-phase circuit the three line currents sum to zero and each conductor carries its own phase current one way. Working the line-to-line drop out from that geometry gives √3, which is 1.732.

What is K in the voltage drop formula?

K is the resistivity constant used in the circular-mil form of the formula, V_drop = (2 × K × I × L) ÷ cmil. It is the direct-current resistance in ohms of a conductor 1000 circular mils in area and 1000 ft long at 75 °C: about 12.9 for copper and 21.2 for aluminium. The K method is a shorthand that lets you work with the conductor area directly instead of looking up a resistance, and it agrees with the table method to within about 1%.

What is the metric voltage drop formula?

V_drop = (2 × ρ × L × I) ÷ A for DC and single-phase, or with √3 in place of the 2 for three-phase. ρ is resistivity in Ω·mm²/m (about 0.0209 for copper at 75 °C and 0.0345 for aluminium), L is the one-way length in metres, I is current in amperes and A is the conductor cross-sectional area in mm². The result is in volts.

Does the voltage drop formula use one-way or total length?

One-way. Every form of the formula on this page takes the distance from the source to the load, and the multiplier, the 2 or the √3, is what accounts for the return path. Substituting a round-trip cable length gives an answer that is twice what it should be.


To see any of these formulas run with your own numbers, and with each substitution written out, use the voltage drop calculator. For five complete examples worked start to finish, see voltage drop calculation.