The one number that matters
Conductivity is measured against a standard: 100% IACS is defined as the conductivity of annealed copper, 1.7241 × 10⁻⁸ Ω·m at 20 °C. Conductor-grade aluminium is 61% IACS, which works out to 2.8264 × 10⁻⁸ Ω·m.
Since resistance is inversely proportional to conductivity, aluminium has 1 ÷ 0.61 = 1.64 times the resistance of copper at the same cross-sectional area. And because voltage drop follows resistance directly, aluminium produces about 64% more drop, size for size.
Resistance, size for size
| Size | Cu Ω/kft | Al Ω/kft | Al ÷ Cu | Cu 75 °C | Al 75 °C |
|---|---|---|---|---|---|
| 12 AWG | 1.98 | 3.25 | 1.64× | 25 A | 20 A |
| 10 AWG | 1.24 | 2.04 | 1.65× | 35 A | 30 A |
| 8 AWG | 0.778 | 1.28 | 1.65× | 50 A | 40 A |
| 6 AWG | 0.491 | 0.808 | 1.65× | 65 A | 50 A |
| 4 AWG | 0.308 | 0.508 | 1.65× | 85 A | 65 A |
| 2 AWG | 0.194 | 0.319 | 1.64× | 115 A | 90 A |
| 1/0 AWG | 0.122 | 0.201 | 1.65× | 150 A | 120 A |
| 2/0 AWG | 0.0967 | 0.159 | 1.64× | 175 A | 135 A |
| 4/0 AWG | 0.0608 | 0.1 | 1.64× | 230 A | 180 A |
| 250 kcmil | 0.0515 | 0.0847 | 1.64× | 255 A | 205 A |
| 350 kcmil | 0.0367 | 0.0605 | 1.65× | 310 A | 250 A |
| 500 kcmil | 0.0258 | 0.0424 | 1.64× | 380 A | 310 A |
Resistance from NEC Chapter 9, Table 8 at 75 °C, Class B stranded. Ampacity from NEC Table 310.16 at the 75 °C column, 30 °C ambient, no more than three current-carrying conductors.
The ratio column sits close to 1.64 all the way down, which is what you would expect from a difference that is purely material rather than geometric.
Equivalent sizes
To match a copper conductor on voltage drop you need enough extra aluminium area to cancel the conductivity difference. Two AWG sizes is the working rule; here is what it looks like against the actual table.
| Copper | Ω/kft | Aluminium match | Ω/kft | Area increase |
|---|---|---|---|---|
| 12 AWG | 1.98 | 8 AWG | 1.28 | 2.53× |
| 10 AWG | 1.24 | 6 AWG | 0.808 | 2.53× |
| 8 AWG | 0.778 | 4 AWG | 0.508 | 2.53× |
| 6 AWG | 0.491 | 3 AWG | 0.403 | 2.01× |
| 4 AWG | 0.308 | 1 AWG | 0.253 | 2.01× |
| 2 AWG | 0.194 | 2/0 AWG | 0.159 | 2.01× |
| 1/0 AWG | 0.122 | 4/0 AWG | 0.1 | 2.00× |
| 2/0 AWG | 0.0967 | 250 kcmil | 0.0847 | 1.88× |
| 4/0 AWG | 0.0608 | 350 kcmil | 0.0605 | 1.65× |
Computed from NEC Chapter 9, Table 8 values at 75 °C. The aluminium size listed is the smallest whose resistance is at or below the copper conductor’s.
The area increase column hovers around 1.6, which is the conductivity ratio showing up exactly where you would expect it. The match is not always precisely two AWG sizes because the AWG series steps in fixed ratios that do not line up perfectly with 1.64, which is why it is worth checking the table rather than applying the rule blindly on a close call.
Ampacity
Higher resistance means more heat for the same current, so aluminium’s allowable ampacity is lower size for size. The ratio is not the same 1.64, because ampacity is set by heat dissipation, which depends on surface area and insulation rating as well as on resistance.
In practice the ampacity substitution lands in roughly the same place as the voltage drop substitution: about two AWG sizes. But they are separate constraints and it is worth confirming both, which is what the wire size calculator does.
Weight and handling
Aluminium’s density is about 2.70 g/cm³ against copper’s 8.96, roughly 30%. Even after going up two sizes to compensate for conductivity, an aluminium conductor of equivalent capacity weighs around half what the copper one does.
On a 400 ft feeder of large conductor, pulled by hand, that is the difference between a routine pull and a difficult one. It is a genuine engineering consideration, not a footnote, and combined with the cost difference it is why large feeders and service entrances are so often aluminium.
Terminations
This is where aluminium demands more care, and where its reputation came from.
Oxide layer
Aluminium forms an oxide film on contact with air. Unlike copper oxide, aluminium oxide is an insulator and it re-forms almost immediately. A termination has to break through that film and keep it from re-forming, which is what antioxidant compounds and the mechanical action of a properly torqued connector are for.
Creep
Aluminium deforms slowly under sustained pressure. A joint torqued correctly on installation day can loosen over months as the metal flows away from the pressure point. A loose joint has resistance, resistance means heat, and heat accelerates the creep. Connectors listed for aluminium are designed around this.
Galvanic corrosion
Aluminium and copper in direct contact with moisture present form a galvanic couple, and the aluminium corrodes. A dissimilar-metal joint needs a connector listed for the combination, marked AL/CU or equivalent.
Thermal expansion
Aluminium expands and contracts more than copper with temperature. A joint that cycles daily works itself loose faster if the connector was not designed for the movement.
Which to use
| Copper | Aluminium | |
|---|---|---|
| Typical use | Branch circuits, short runs, tight raceways | Service entrances, large feeders, long runs |
| Size for a given job | Smaller | About two AWG sizes larger |
| Weight for a given job | Roughly twice | Roughly half |
| Cost per unit capacity | Higher | Lower: the main reason it is chosen |
| Termination | Straightforward | Listed connectors, correct torque, antioxidant where specified |
| Raceway space | Less | More: may drive a larger conduit |
The decision usually resolves itself by scale. On a branch circuit the cost saving is trivial and the extra size is a nuisance, so copper wins. On a 400 A service entrance the cost saving is substantial and the weight saving is the difference between a manageable pull and a miserable one, so aluminium wins. Between those extremes, run both through the calculator and compare.
Questions
How much more voltage drop does aluminium have than copper?
About 64% more at the same conductor size. Conductor-grade aluminium is rated 61% IACS against copper’s 100%, so its resistance is roughly 1.64 times copper’s for the same cross-sectional area, and voltage drop follows resistance directly. For example, 2 AWG copper is 0.194 Ω per 1000 ft while 2 AWG aluminium is 0.319.
What size aluminium wire equals copper?
Two AWG sizes larger is the usual rule for matching on voltage drop, and it is close. 2 AWG copper at 0.194 Ω per 1000 ft is matched by 1/0 aluminium at 0.201; 4/0 copper at 0.0608 is matched by 300 kcmil aluminium at 0.0707 or 350 kcmil at 0.0605. Ampacity generally works out to roughly the same substitution, but check both rather than assuming.
Is aluminium wire safe?
Modern aluminium building wire, the AA-8000 series alloys used since the 1970s, is a standard, listed conductor material used routinely in feeders and service entrances. The problems associated with aluminium came from the older AA-1350 alloy used in branch circuits in the 1960s and 70s, combined with terminations that were not designed for it. The material is not the issue; the termination method is, and it has to be right.
Why is aluminium used at all if copper is better?
Cost and weight. Aluminium costs substantially less per unit of current-carrying capacity, and it is roughly half the weight of a copper conductor of equivalent ampacity even though it is physically larger. On a long, large feeder those two things dominate: the conductor is a major line item and it has to be pulled by hand. This is why service entrances and large feeders are commonly aluminium while branch circuits are commonly copper.
Can I terminate aluminium and copper together?
Only with a connector listed for the purpose. Aluminium and copper in direct contact in the presence of moisture form a galvanic couple that corrodes the aluminium, and aluminium also creeps under pressure, which loosens a joint over time. Use connectors marked AL/CU or a listed splice designed for a dissimilar-metal joint, follow the manufacturer’s torque specification, and use an antioxidant compound where it is specified.
Switch material on the voltage drop calculator to see the difference on your own circuit, or let the wire size calculator pick the size for each.