Reference tables

Voltage Drop Chart

A voltage drop chart is only as good as the numbers behind it. Every figure on this page is either computed live by the same engine the calculators use, or cited to the table it came from. Nothing is transcribed from another chart.

System
Material
Sizes
Distance in
V
A
%

Voltage drop percentage on a 120 V single-phase circuit at 20 A, copper conductors in AWG sizes, one-way distance. Anything above 3% is marked.

Voltage drop percentage by conductor size and one-way distance
Size25 ft50 ft75 ft100 ft150 ft200 ft250 ft300 ft400 ft500 ft
14 AWG2.62%5.23%, over limit7.85%, over limit10.47%, over limit15.70%, over limit20.93%, over limit26.17%, over limit31.40%, over limit41.87%, over limit52.33%, over limit
12 AWG1.65%3.30%, over limit4.95%, over limit6.60%, over limit9.90%, over limit13.20%, over limit16.50%, over limit19.80%, over limit26.40%, over limit33.00%, over limit
10 AWG1.03%2.07%3.10%, over limit4.13%, over limit6.20%, over limit8.27%, over limit10.33%, over limit12.40%, over limit16.53%, over limit20.67%, over limit
8 AWG0.65%1.30%1.95%2.59%3.89%, over limit5.19%, over limit6.48%, over limit7.78%, over limit10.37%, over limit12.97%, over limit
6 AWG0.41%0.82%1.23%1.64%2.46%3.27%, over limit4.09%, over limit4.91%, over limit6.55%, over limit8.18%, over limit
4 AWG0.26%0.51%0.77%1.03%1.54%2.05%2.57%3.08%, over limit4.11%, over limit5.13%, over limit
3 AWG0.20%0.41%0.61%0.82%1.23%1.63%2.04%2.45%3.27%, over limit4.08%, over limit
2 AWG0.16%0.32%0.48%0.65%0.97%1.29%1.62%1.94%2.59%3.23%, over limit
1 AWG0.13%0.26%0.38%0.51%0.77%1.03%1.28%1.54%2.05%2.57%
1/0 AWG0.10%0.20%0.31%0.41%0.61%0.81%1.02%1.22%1.63%2.03%
2/0 AWG0.08%0.16%0.24%0.32%0.48%0.64%0.81%0.97%1.29%1.61%
3/0 AWG0.06%0.13%0.19%0.26%0.38%0.51%0.64%0.77%1.02%1.28%
4/0 AWG0.05%0.10%0.15%0.20%0.30%0.41%0.51%0.61%0.81%1.01%

Computed with the site calculator from NEC Chapter 9, Table 8 direct-current resistance at 75 °C. Resistance only. See the AC calculator for results including conductor reactance.

Per amp, per 100 ft

The figure you can do arithmetic with.

Volts dropped per ampere per 100 ft of one-way run on a two-wire circuit. Multiply by your current and by your run length in hundreds of feet, and you have the drop in volts.

Voltage drop per ampere per 100 ft for copper and aluminium conductors
SizeAreaCircular milsCopperAluminiumAl ÷ Cu
18 AWG0.82 mm²1,6201.59 V2.62 V1.65×
16 AWG1.31 mm²2,5800.998 V1.642 V1.65×
14 AWG2.08 mm²4,1100.628 V1.034 V1.65×
12 AWG3.31 mm²6,5300.396 V0.65 V1.64×
10 AWG5.26 mm²10,3800.248 V0.408 V1.65×
8 AWG8.37 mm²16,5100.1556 V0.256 V1.65×
6 AWG13.30 mm²26,2400.0982 V0.1616 V1.65×
4 AWG21.15 mm²41,7400.0616 V0.1016 V1.65×
2 AWG33.62 mm²66,3600.0388 V0.0638 V1.64×
1/0 AWG53.49 mm²105,6000.0244 V0.0402 V1.65×
2/0 AWG67.43 mm²133,1000.01934 V0.0318 V1.64×
4/0 AWG107.20 mm²211,6000.01216 V0.02 V1.64×
250 kcmil127.00 mm²250,0000.0103 V0.01694 V1.64×
500 kcmil253.00 mm²500,0000.00516 V0.00848 V1.64×

Computed as 2 × R × 0.1 from NEC Chapter 9, Table 8 direct-current resistance at 75 °C, Class B stranded. For three-phase, multiply by √3 ÷ 2 = 0.866.

Conductor resistance

AWG and kcmil sizes.

Direct-current resistance at 75 °C, per conductor. Both stranding classes are listed for the sizes manufactured either way.

Conductor resistance for AWG and kcmil sizes, copper and aluminium
Sizemm²Cu solid
Ω/kft
Cu stranded
Ω/kft
Cu stranded
Ω/km
Al stranded
Ω/kft
Al stranded
Ω/km
18 AWG0.827.777.9526.0813.142.98
16 AWG1.314.894.9916.378.2126.94
14 AWG2.083.073.1410.35.1716.96
12 AWG3.311.931.986.4963.2510.66
10 AWG5.261.211.244.0682.046.693
8 AWG8.370.7640.7782.5521.284.199
6 AWG13.300.4911.6110.8082.651
4 AWG21.150.3081.010.5081.667
3 AWG26.670.2450.80380.4031.322
2 AWG33.620.1940.63650.3191.047
1 AWG42.410.1540.50520.2530.8301
1/0 AWG53.490.1220.40030.2010.6594
2/0 AWG67.430.09670.31730.1590.5217
3/0 AWG85.010.07660.25130.1260.4134
4/0 AWG107.200.06080.19950.10.3281
250 kcmil127.000.05150.1690.08470.2779
300 kcmil152.000.04290.14070.07070.232
350 kcmil177.000.03670.12040.06050.1985
400 kcmil203.000.03210.10530.05290.1736
500 kcmil253.000.02580.084650.04240.1391
600 kcmil304.000.02140.070210.03530.1158
700 kcmil355.000.01840.060370.03030.09941
750 kcmil380.000.01710.05610.02820.09252
800 kcmil405.000.01610.052820.02650.08694
900 kcmil456.000.01430.046920.02350.0771
1000 kcmil507.000.01290.042320.02120.06955

NFPA 70 (National Electrical Code), Chapter 9, Table 8 (Conductor Properties). Direct-current resistance at 75 °C (167 °F). Values there are calculated per National Bureau of Standards Handbook 100 (1966) and Handbook 109 (1972), at 100% IACS for copper and 61% IACS for aluminium.

Conductor resistance

Metric mm² sizes.

These are calculated, not looked up. No published table on this site covers IEC conductor sizes, so the figures come from resistivity, and the page says so rather than presenting them as tabulated values.

Calculated conductor resistance for metric sizes, copper and aluminium
SizeCircular milsCopper
Ω/km
Copper
Ω/kft
Aluminium
Ω/km
Aluminium
Ω/kft
0.5 mm²98741.9412.7869.0621.05
0.75 mm²1,48027.968.52146.0414.03
1 mm²1,97420.976.39134.5310.52
1.5 mm²2,96013.984.26123.027.016
2.5 mm²4,9348.3872.55613.814.21
4 mm²7,8945.2421.5988.6322.631
6 mm²11,8413.4951.0655.7551.754
10 mm²19,7352.0970.63913.4531.052
16 mm²31,5761.310.39942.1580.6578
25 mm²49,3380.83870.25561.3810.421
35 mm²69,0730.59910.18260.98650.3007
50 mm²98,6760.41940.12780.69060.2105
70 mm²138,1470.29950.09130.49330.1503
95 mm²187,4850.22070.067270.36350.1108
120 mm²236,8230.17470.053260.28770.0877
150 mm²296,0290.13980.042610.23020.07016
185 mm²365,1020.11330.034550.18660.05689
240 mm²473,6460.087370.026630.14390.04385
300 mm²592,0580.069890.02130.11510.03508
400 mm²789,4100.052420.015980.086320.02631
500 mm²986,7630.041940.012780.069060.02105

Calculated as R = ρ₂₀ × [1 + α₂₀ × (T − 20)] ÷ A at 75 °C, with ρ₂₀ = 1.7241 × 10⁻⁸ Ω·m for copper (100% IACS) and 2.8264 × 10⁻⁸ Ω·m for aluminium (61% IACS). This models a smooth conductor of the nominal area; real stranded cable reads roughly 2% higher because the strands spiral, and IEC 60228 maximum values allow more again. The same method reproduces NEC Chapter 9 Table 8 solid-conductor values to within 0.2%.

AC values

Resistance and reactance at 60 Hz.

For AC circuits below unity power factor, resistance alone understates the drop. These are the values the AC calculator combines into an effective impedance.

AC resistance and inductive reactance by conductor size and raceway
SizeXL PVC/AlXL steelCu R, PVCCu R, steelAl R, PVCAl R, steel
14 AWG0.0580.0733.13.1
12 AWG0.0540.068223.23.2
10 AWG0.050.0631.21.222
8 AWG0.0520.0650.780.781.31.3
6 AWG0.0510.0640.490.490.810.81
4 AWG0.0480.060.310.310.510.51
3 AWG0.0470.0590.250.250.40.4
2 AWG0.0450.0570.190.20.320.32
1 AWG0.0460.0570.150.160.250.25
1/0 AWG0.0440.0550.120.120.20.2
2/0 AWG0.0430.0540.10.10.160.16
3/0 AWG0.0420.0520.0770.0790.130.13
4/0 AWG0.0410.0510.0620.0630.10.1
250 kcmil0.0410.0520.0520.0540.0850.086
300 kcmil0.0410.0510.0440.0450.0710.072
350 kcmil0.040.050.0380.0390.0610.063
400 kcmil0.040.0490.0330.0350.0540.055
500 kcmil0.0390.0480.0270.0290.0430.045
600 kcmil0.0390.0480.0230.0250.0360.038
750 kcmil0.0380.0480.0190.0210.0290.031
1000 kcmil0.0370.0460.0150.0180.0230.025

NFPA 70, Chapter 9, Table 9, Alternating-Current Resistance and Reactance for 600-Volt Cables, 3-Phase, 60 Hz, 75 °C, three single conductors in conduit. Ohms to neutral per 1000 ft, Class B stranded RHH in a cradled configuration. Capacitive reactance is ignored as negligible at these voltages. Effective Z is computed as R cos θ + X sin θ at 0.85 power factor.

Ampacity

What each size may carry.

A separate question from voltage drop, included here because a conductor has to satisfy both. These are base table values before any correction or adjustment factor.

Allowable ampacity by conductor size, material and temperature rating
SizeCu 60 °CCu 75 °CCu 90 °CAl 60 °CAl 75 °CAl 90 °C
14 AWG152025
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350
600 kcmil350420475285340385
750 kcmil400475535320385435
1000 kcmil455545615375445500

NFPA 70, Table 310.16. Allowable ampacities of insulated conductors rated up to 2000 V, not more than three current-carrying conductors in a raceway, cable or earth, at 30 °C (86 °F) ambient. Correction factors for ambient temperature, adjustment factors for conductor count, terminal temperature limitations under 110.14(C), and the small-conductor rules of 240.4(D) are not applied.

How to read these charts

Distance is one-way

Every distance in these tables is the distance from the source to the load. The formulas already double it for the return conductor. Entering a total cable length as if it were a one-way figure is the most common way to get an answer that is twice what it should be.

Resistance is at 75 °C

Conductor resistance rises with temperature. A conductor running cool drops less than these figures show, one running hot drops more. The main calculator applies the NEC Chapter 9 Table 8 Note 2 correction if you tell it the operating temperature.

Reactance is not included in the matrix

The size-by-distance chart uses resistance only. That is exact for DC and for AC at unity power factor. For inductive loads, use the AC calculator, which combines resistance and reactance at your power factor.

These are calculations, not measurements

A real run also has resistance at every termination, splice and device. Expect a measured drop somewhat higher than a calculated one. If it is far higher, the problem is usually a connection rather than the conductor. See how to measure voltage drop.

Questions

Common questions.

How do you read a voltage drop chart?

Find the row for your conductor size and the column for your material or distance, and read the figure. The tables here give volts dropped per ampere per 100 ft, so multiply the figure by your load current and by your run length in hundreds of feet. A 10 AWG copper conductor at 0.24 V per amp per 100 ft carrying 15 A over 60 ft drops 0.24 × 15 × 0.6 = 2.16 V.

What is the voltage drop per 100 feet of wire?

It depends on the conductor size, the material and the current, which is why a chart is indexed by size rather than giving one number. The per-ampere figure is fixed for a given size and material, so the chart states that and you supply the current. Doubling the current doubles the drop, and doubling the conductor area roughly halves it.

Are voltage drop charts accurate?

They are accurate for the conditions they were built on and only those. The tables here assume 75 °C conductor temperature, resistance only with no reactance term, and the distance measured one way. A run at a different temperature, an inductive load below unity power factor, or a large conductor in steel conduit will differ. Use a chart to narrow the choice and the calculator to confirm it.

What is the difference between a voltage drop chart and a wire size chart?

A voltage drop chart starts from a conductor size and tells you the drop it produces. A wire size chart works the other way, starting from a load and a distance and giving a size that will meet a stated drop limit. They answer opposite questions from the same underlying data, and a wire size figure always carries an assumed voltage, current and drop limit that has to match your circuit for the answer to hold.